Cable Runway

Cable RunwayCable Runway supports backbone and horizontal cables between the point of entry and exit into the telecommunications or equipment rooms and cross-connects on racks or cabinets with CPI Cable Runway Products. A wide selection of supports, splices and accessories are available.

eCatalog

Features include:

  • Constructed of rectangular steel tubing for strength and support
  • 132 lb/ft maximum load with runway supported every five feet
  • Individually boxed to prevent scratching and damage
  • Meets ANSI/TIA/EIA installation guidelines

Sales Support

Contact Sales Support if you have questions about:

  • Product Orders 
  • Distributors & Resellers

In the U.S. call 1-800-834-4969, outside the U.S. & Canada, call +818-739-3400.

Or you can submit a Customer Support Request.

Find a CPI Sales Rep Near You

Model
Description
Product Cut Sheet
Features
Installation Practice
Material Composition & Design
Load Capacity
Recommended Cable Capacity of Cat 6a Cables at 50% Fill
Overall Length
Choice of Widths
Cable Runway
Cable Runway
Cable Runway supports backbone and horizontal cables between the point of entry and exit into the telecommunications or equipment rooms and cross-connects on racks or cabinets with CPI Cable Runway Products. A wide selection of supports, splices and accessories are available.
Flat design with cross members providing a flat surface for easy data cable transition. Simple pathway design and assembly; straight sections are spliced to change pathway direction. Three styles: Universal, Telco, and UL Classified
Pathway is manually field fabricated. Splices, transitions and intersections use a specific splice kit. The only accessories required to couple sections of cable runway together are a Splice Kit and a single Ground Strap to electrically Bond the two sections together. UL Classified Cable Runway bonds with splices. Support required every 5' (1.5 m)
Made of heavy duty, lightweight tubular steel with cross members welded every 12" (300 mm) on Universal Cable Runway and every 9" (228 mm) on Telco and UL Classified Cable Runways. Due to the resilient construction of CPI's Cable Runway, sections can be modified by cutting, shortening and trimming with zero detrimental effect to the ladders weight load capacity.
132 lb/ft with support every 5' 200 kg/m with support every 1.5 m
From 85 to 509 depending on width.
9’ 11.5” (3035 mm), Universal 9’ 8.5” (2959 mm), Telco & UL Classified
4" (100 mm), Universal only 6" (150 mm), Universal, Telco, UL 9" (230 mm), Universal, Telco, UL 10" (250 mm), Telco only 12" (300 mm), Universal, Telco, UL 15" (380 mm), Universal, Telco, UL 18" (460 mm), Universal, Telco, UL 20" (510 mm), Telco & UL only 24" (610 mm), Universal & UL only 30" (760 mm), Universal only 36" (910 mm), Universal only
OnTrac® Wire Mesh Cable Tray
OnTrac Wire Mesh Cable Tray
Wire Mesh Cable Tray Products provide point-to-point pathways for network cabling in data centers, network equipment rooms and office spaces.
Trough style design; various heights are available. Flexible pathway; cut and bend straight sections to change pathway direction.
Pathway is manually field fabricated. Splices, transitions and intersections require careful planning. To couple sections of OnTrac together a combination of Standard Splice Kits, Splice Bars, Splice Washer & Bolt Kit, Clamp Washers, and Carriage Bolt Hardware Kits are required depending on the type of splice. A ground strap is required to bond sections when tray is removed to create a splice or transition. Support required every 5' (1.5 m)
Made of 5mm and 6mm round steel wire welded into a 2" x 4" (50 mm x100 mm) rectangular grid pattern. The tray load capacity for basket tray may be lessened as a result of any field modification. Once the wire mesh is cut, the load is de-rated.
Varies according to height and width. Refer to the product data sheet.
Varies from 29 to 507 depending on width and height.
10' (250 mm)
4" (100 mm) 6" (150 mm) 8" (200 mm) 12" (300 mm) 16" (400 mm) 18"(450 mm) 20" (500 mm) 24" (600 mm)